Revision 10 ST 800 SmartLine Pressure Transmitters User’s Manual Page 43
Enter LRV
<Return>
Enter LRV
###. ##
The limit for the Lower Range
Value is 2X the Lower Range
Limit (LRL) of the Meterbody
Enter URV
<Return>
Enter URV
###. ##
The limit for the Upper Range
Value is 2X the Upper Range
Limit (URL) of the Meterbody
Set LRV
<Return>
Set LRV
ATTENTION: Executing this service will set the
Lower Range Value (LRV) equal to the input
pressure
Press to enter
menu selection
to execute
Set URV
<Return>
Set URV
ATTENTION: Executing this service will set the
Upper Range Value (URV) equal to the input
pressure
Press to enter
menu selection
to execute
HART Setup
<Return>
Device ID
Unique for each device
Read Only
Universal Rev
HART Revision
Read Only
Field Device Rev
For DD/DTM compatibility
Read Only
Final Assy Num
Asset tracking number
Loop mA
Disabled for Multidrop
Poll Address
0 (default) to 63
PV Units
Units of transmitted PV
SV Units
Units of transmitted SV
HART Date
<Return>
Year
# # # #
Enter the current year.
Month
January thru
December
Select the current
month.
Day
# #
Enter the day of the
month.
Write Date
Press ENTER to write the HART Date to the
transmitter.