Revision 10 ST 800 SmartLine Pressure Transmitters User’s Manual Page 45
PILD
(Available only
if the PILD
Option is
enabled)
Sample
Window
##
The sampling window
of PILD in minutes,
which determines the
cycle of PILD runs for
both training and
monitoring mode.
Enter the sample
window Value.
Range: 3 mins,
6 mins, 9 mins, 12
mins, 15 mins.
See Note below.
Press to enter
menu selection
and to select
number.
to enter and
shift to next digit.
Up Limit
#.##
The up limit of PILD
factor for normal
status..
Enter the Up Limit
Value.
Range: 0.50 to 1.00.
See Note below.
Press to enter
menu selection
and to select
number.
to enter and
shift to next digit
Down Limit
#.##
The Down limit of PILD
factor for normal
status..
Enter the Down Limit
Value.
Range: Both Limit to
0.50
See Note below.
Press to enter
menu selection
and to select
number.
to enter and
shift to next digit
Both Limit
#.##
The Both sides
blockage limit of PILD.
Enter the Both Limit
Value.
Range: 0.00 to Down
Limit.
It is applicable for only
DP Transmitter.
See Note below.
Press to enter
menu selection
and to select
number.
to enter and
shift to next digit
HPF f0
#.#
The High Pass Filter
(HPF) Cutoff Frequency
(f
0
) reduces noise
fluctuations in the PILD
Factor measured value.
Enter the HPF f0
Value.
Range: 0.0 to 5.0.
See Note below.
Press to enter
menu selection
and to select
number.
to enter and
shift to next digit
Note:
This parameter will be “Read Only” when the user configures PILD as Enabled in this sub menu. An attempt to
configure this parameter will then invoke the pop-up message”Read Only! PILD Active”. The parameters Up