Revision 10 ST 800 SmartLine Pressure Transmitters User’s Manual Page 51
Transfer Function
(only available for
DP Transmitters)
Linear
The loop output of the transmitter
is a linear representation of the
differential pressure
Press to enter
menu selection
and to select
Alphanumeric
to enter and
shift to next
character to the
right.
Square Root
The loop output of the transmitter
represents %Flow as defined by
the DP Square Root flow equation.
Flow Cutoff
Single Breakpt
Allows the user to specify a single
breakpoint as the low flow cutoff
point. This item is only available
when the Transfer Function is set
to Square Root.
Dual Slope
Uses a dual slope formula to
determine the low flow cutoff point.
This item is only available when
the Transfer Function is set to
Square Root.
Flow Breakpoint
##. #%
Enter the low flow cutoff point
when Single Breakpt is selected.
Range: 0 to 25.0 %Flow.
Tag ID

Enter Tag ID name up to 8
characters long.
= any Alphanumeric value
Press to enter
menu selection
and to select
Alphanumeric
to enter and
shift to next
character to the
right.
HART Device ID
Unique for each device
Read Only
HART PV Units
Units of transmitted PV
PILD
(optional)
Enabled
Disabled
This selection allows the user to
enable or disable PILD detection.
This item will be available only if
the PILD option is enabled.
Press to enter
menu selection
and to select
from list
to enter
Serial Number
Unique serial number for the transmitter
Read only
License key
# # # # # # # #
License key to enable PILD option
Write only
Install Date
DD MM YYYY
This selection allows the user to
enter the date a transmitter is
installed.
The Install Date is entered in
sequence of Day, Month, and
Year, followed by the new date
and the prompt Write Date to
confirm the entry.
CAUTION: The Install Date can
only be written once in the life of
the Transmitter. You cannot erase
or overwrite the Install Date once it
has been written.
Press to enter
menu selection
and to select
number
to enter and
shift to next digit
to the right.
Read Only after
entered