Page 50 ST 800 SmartLine Pressure Transmitters User’s Manual Revision 10
Shows one of the
option below:
Cal Set A
Cal Set B
Cal Set C
Best Fit
Displays the current calibration
used by the sensor.
Cal Set B is only available with
dual calibration
Cal Set C is only available with
triple calibration
Cal Set A
Cal Set B
Cal Set C
Best Fit
This selection allows the user to
choose calibration type from the
list.
Cal Set B is only available with
dual calibration
Cal Set C is only available with
triple calibration
Press to enter
menu selection
and to select
from list
to enter
Note: Loop must be
removed from
Automatic Control
This selection allows the loop zero
output 4mA value to be trimmed.
Note: You must connect a current
meter to the transmitter to monitor
the loop output.
Press to enter
menu selection
and to select
number.
to enter and
shift to the next
digit to the right
Note: Loop must be
removed from
Automatic Control
This selection allows the loop
span output 20mA value to be
trimmed.
Note: You must connect a current
meter to the transmitter to monitor
the loop output.
Note: Loop must be
removed from
Automatic Control
This selection allows the user to
force the DAC output to any value
between 3.8 and 20.8 mA.
Note: This selection will put the
DAC into Fixed Output Mode, as
indicated by the flashing output
value. Navigation away from this
menu item will return the loop to
Normal (Automatic) Mode.
2X the Lower Range Limit (LRL) of
the Meterbody and 2X the Upper
Range Limit (URL) of the
Meterbody
Press to enter
menu selection
and to select
number.
to enter and
shift to the next
digit to the right
Selection applies digital filtering to
suppress noise effects on the PV.
The limits for this value are 0.0 to
32.0 seconds
Disabling sets the loop output and
burnout levels to the Honeywell
levels
Press to enter
menu selection
and to select
from list
to enter
Standard Speed of Response