Configuration points for Point sharing47
Cfg_NetOATFailDetDly0….3600
Seconds
600 SecBacnet
Numeric
Value
271Network Fail Detection delay
in seconds
Cfg_NetOAHumFailDet
En
0 = Disable, 1 =
Enable
0Bacnet
Boolean
Value
162Network Fail Detection will be
enabled only if network point
is considered for sharing
Cfg_NetOAHumFailFal
bck
0 = InvalidValue
(Null)
1 =
LastKnownGoo
dValue
2 = FixedValue
0Bacnet
Numeric
Value
267Network Fail Detection Fall
back value
Cfg_NetOAHumFailFxd
Val
0~100 %RHnanBacnet
Numeric
Value
269Applicable only if Network Fail
Fall back value is configured
to Fixed value (2)
Cfg_NetOAHumFailDet
Dly
0….3600
Seconds
600 SecBacnet
Numeric
Value
268Network Fail Detection delay
in seconds
Cfg_NetShtdwnFailDet
En
0 = Disable, 1 =
Enable
0Bacnet
Boolean
Value
164Network Fail Detection will be
enabled only if network point
is considered for sharing
Cfg_NetShtdwnFailFal
bck
0 = InvalidValue
(Null)
1 =
LastKnownGoo
dValue
2 = FixedValue
0Bacnet
Numeric
Value
273Network Fail Detection Fall
back value
Cfg_NetShtdwnFailFxd
Val
0=Normal
1=Shutdown
0Bacnet
Boolean
Value
165Applicable only if Network Fail
Fall back value is configured
to Fixed value (2)
Cfg_NetShtdwnFailDet
Dly
0….3600
Seconds
300 SecBacnet
Numeric
Value
274Network Fail Detection delay
in seconds
Cfg_NetSpceCO2FailD
etEn
0 = Disable, 1 =
Enable
0Bacnet
Boolean
Value
166Network Fail Detection will be
enabled only if network point
is considered for sharing
Cfg_NetSpceCO2FailF
albck
0 = InvalidValue
(Null)
1 =
LastKnownGoo
dValue
2 = FixedValue
0Bacnet
Numeric
Value
275Network Fail Detection Fall
back value
Cfg_NetSpceCO2FailF
xdVal
0~2000 PPMnanBacnet
Numeric
Value
277Applicable only if Network Fail
Fall back value is configured
to Fixed value (2)
Table 25: Configuration points for Point sharing (Continued)
NameRange
Default
Value
BACnet
Point
Type
BACnet
Object
Instance
ID
Description

Table of Contents

Other manuals for Honeywell TC500A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell TC500A and is the answer not in the manual?

Honeywell TC500A Specifications

General IconGeneral
BrandHoneywell
ModelTC500A
CategoryThermostat
LanguageEnglish

Related product manuals