48Configuration points for Point sharing
Cfg_NetSpceCO2FailD
etDly
0….3600
Seconds
600 SecBacnet
Numeric
Value
276Network Fail Detection delay
in seconds
Cfg_NetSpceRHFailDet
En
0 = Disable, 1 =
Enable
0Bacnet
Boolean
Value
167Network Fail Detection will be
enabled only if network point
is considered for sharing
Cfg_NetSpceRHFailFal
bck
0 = InvalidValue
(Null)
1 =
LastKnownGoo
dValue
2 = FixedValue
0Bacnet
Numeric
Value
278Network Fail Detection Fall
back value
Cfg_NetSpceRHFailFxd
Val
0~100% RHnanBacnet
Numeric
Value
280Applicable only if Network Fail
Fall back value is configured
to Fixed value (2)
Cfg_NetSpceRHFailDet
Dly
0….3600
Seconds
600 SecBacnet
Numeric
Value
279Network Fail Detection delay
in seconds
Cfg_NetSpceTmpFailD
etEn
0 = Disable, 1 =
Enable
0Bacnet
Boolean
Value
168Network Fail Detection will be
enabled only if network point
is considered for sharing
Cfg_NetSpceTmpFailF
albck
0 = InvalidValue
(Null)
1 =
LastKnownGoo
dValue
2 = FixedValue
0Bacnet
Numeric
Value
281Network Fail Detection Fall
back value
Cfg_NetSpceTmpFailF
xdVal
-40~140 Deg FnanBacnet
Numeric
Value
283Applicable only if Network Fail
Fall back value is configured
to Fixed value (2)
Cfg_NetSpceTmpFailD
etDly
0….3600
Seconds
600 SecBacnet
Numeric
Value
282Network Fail Detection delay
in seconds
Cfg_NetWSHPEnStFail
DetEn
0 = Disable, 1 =
Enable
0Bacnet
Boolean
Value
169Network Fail Detection will be
enabled only if network point
is considered for sharing
Cfg_NetWSHPEnStFail
Falbck
0 = InvalidValue
(Null)
1 =
LastKnownGoo
dValue
2 = FixedValue
0Bacnet
Numeric
Value
284Network Fail Detection Fall
back value
Cfg_NetWSHPEnStFail
FxdVal
0=Disable
1=Enable
0Bacnet
Boolean
Value
170Applicable only if Network Fail
Fall back value is configured
to Fixed value (2)
Table 25: Configuration points for Point sharing (Continued)
NameRange
Default
Value
BACnet
Point
Type
BACnet
Object
Instance
ID
Description

Table of Contents