Configuration points for Point sharing49
Cfg_NetWSHPEnStFail
DetDly
0….3600
Seconds
900 SecBacnet
Numeric
Value
285Network Fail Detection delay
in seconds
Cfg_NetWSHPEnValFai
lDetEn
0 = Disable, 1 =
Enable
0Bacnet
Boolean
Value
171Network Fail Detection will be
enabled only if network point
is considered for sharing
Cfg_NetWSHPEnValFai
lFalbck
0 = InvalidValue
(Null)
1 =
LastKnownGoo
dValue
2 = FixedValue
0Bacnet
Numeric
Value
286Network Fail Detection Fall
back value
Cfg_NetWSHPEnValFai
lFxdVal
0~100 %nanBacnet
Numeric
Value
287Applicable only if Network Fail
Fall back value is configured
to Fixed value (2)
Cfg_NetWSHPEnValFai
lDetDly
0….3600
Seconds
600 SecBacnet
Numeric
Value
288Network Fail Detection delay
in seconds
Table 25: Configuration points for Point sharing (Continued)