General network outputs61
no_SpaceCO20-2000 PPMNullBACnet
Numeric
Output
20Space CO2
no_EconEn0=Disable
1=Enable
Disable (0)BACnet
Boolean
Output
22Economizer Enable output
no_ApplicationCommand
Mode
1=StartupWait
2=Heat
3=Cool
4=Off
5=EmgHt
6=SmkEmg
7= Freeze
Protect
8=Service
Mode
9 = FanOnly
4=OffBACnet
ENUM Value
8Gives out the current
application mode
no_CtrlSpaceTemp-40~140 Deg
F
NullBACnet
Numeric
Output
67Control Space Temperature
output (Only for testing
purpose)
no_RecoveryStatus0 = Normal
1 = Recovery
Inactive
(Normal)
BACnet
Boolean
Output
82This point gives out when the
system is in recovery mode.
no_IsFreeCoolAvailable0 = Not
Available
1= Available
Inactive
(Not
Avialable)
BACnet
Boolean
Output
86This point gives the status
whether free cooling is
available or not.
no_CompCurSens0~100 AmpsNullBACnet
Numeric
Output
71This point gives out the
Comp Current Sensor value
from the terminal input.
no_FanCurSens0~100 AmpsNullBACnet
Numeric
Output
72This point gives out the Fan
Current Sensor value from
the terminal input.
no_OccupancySensor1=Occupied
0=Unoccupied
NullBacnet
Boolean
Output
94This point is considered for
Network point sharing of
Occupancy sensor status of
terminal
no_ShutdownState0=NoOvrd
1=ShutdownE
n
NullBacnet
Boolean
Output
95This point is considered for
Network point sharing of
shutdown state of terminal
no_WSHPEnableState0 = Disable
1 = Enable
NullBacnet
Boolean
Output
96This point is considered for
Network point sharing of
WSHP state through
Waterflow status
Table 29: General network outputs (Continued)
NameRange
Default
Value
BACnet
Point Type
BACnet
Object
Instance
ID
Description