Certifications 
MAN0984_Iss 4_01/19  Touchpoint Plus 
Pt. No. 3011M5001  127  Technical Handbook 
Chapter 12. 
12.1 EU Declaration of Conformity 
A full EC declaration of conformity is available on either original hardcopy or electronic file (Honeywell Analytics 
website). This document lists the European Standards with which Touchpoint Plus complies. 
12.2 National and International Certificates of Compliance 
The Touchpoint Plus Process Control Equipment holds the following National and International Certificates and 
Certification Codes: 
Hazardous 
Locations 
(Non-Incendive) 
Class 1, Division 2, Groups A,B,C,D, Temp. Code T4 
ISA 12.12.01-2013 
CSA C22.2 No. 213-M1987 
Ordinary Locations / 
Electrical Safety 
UL/IEC/EN 61010-1, UL 508 
CSA C22.2 No.61010-1/No.142 
UL File E466771 
UL File E470577 
EMC Directive (EN 50270:2015) 
UN 38.3 (IEC 62133), UL 2054, UL 60950-1 
CSA C22.2 No.60950-1-07 
ISA 12.13.01 and CSA C22.2 No.152 
UL File E466771 and 
E480011 
EN 60079-29-1, EN 50104, EN 45544-1/2/3 and EN 50271 
BVS 17 ATEX G 001 X, 
PFG 17 G 002 X 
Designed to meet IEC/EN61508:2010 and SIL2 certification 
Copies of the certificates are available on request. 
Note 1: OEMs are responsible for ensuring that their systems are certified in accordance with these tables and 
any 3
rd
-party requirements. 
WARNING 
Only the combustible gas detection portion of this instrument has been assessed for performance 
in accordance with the ATEX Directive. 
AVERTISSEMENT 
Seulement la 
WARNING 
CSA performance is only valid when TPPL is connected to Honeywell Model MPD or 705 Catalytic 
Gas Detectors, or suitably approved 4   20 mA Gas Detectors. 
AVERTISSEMENT 
z catalytiques Honeywell modèle MPD ou 705, ou à des détecteurs de gaz 4