Commissioning
MAN0984_Iss 4_01/19 Touchpoint Plus
Pt. No. 3011M5001 61 Technical Handbook
6.10 TPPL TCP/IP Address
The default TPPL TCP/IP address (for optional Web Interface access) is 192.168.0.100, but you may need to change
it if it conflicts with other items on the network or if the Control Room is monitoring multiple TPPL systems. See
Ch.6.11 Network Settings for Web and MODBUS TCP and Ch.6.12 Modbus RTU Settings for further information.
6.11 Network Settings for WEB and MODBUS TCP
TPPL can be installed with the ability to view its status over the Web. (See Ch.7.17 Monitoring TPPL via the Optional
Web Interface for more details.)
ystem from unauthorised access or
tampering.
Note: It is important to ensure that the default IP Address does not clash with other units on your network.
To check or set the IP Address:
1) Log in as Administrator or Service
2) Menu>Configuration>Network>Ethernet
3) Touch a radio button to set the IP acquiring type (DHCP / SIP)
4) Touch the IP Address box to change the address (only if there are network conflicts) and enter the new IP Address
using the onscreen keyboard:
5) Touch [Finish]
6) Touch the Subnet Mask and Gateway boxes (if required), and use the keyboard to enter new values as before
7) Touch [Finish]
8) [Log out]

Table of Contents

Other manuals for Honeywell Touchpoint Plus

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Touchpoint Plus and is the answer not in the manual?

Honeywell Touchpoint Plus Specifications

General IconGeneral
MountingPanel
CommunicationEthernet
Communication Ports1 x Ethernet, 2 x USB
Power Supply24 VDC
Enclosure RatingIP65 (front)

Related product manuals