MAN0984_Iss 4_01/19 Touchpoint Plus
Pt. No. 3011M5001 45 Technical Handbook
Module Label
Terminal
Ident
Field device
Module Label
Terminal
Ident
Field device
mA Input 1
1
+VE
+24 VDC
mV Input 1
13
S
Sensitive (+)
2
VE
0 VDC
14
01
Signal
3
Sig
Signal (4 20 mA)
15
NS
Sensitive ( )
mA Input 2
4
+VE
+24 VDC
mV Input 2
16
S
Sensitive (+)
5
VE
0 VDC
17
01
Signal
6
Sig
Signal (4 20 mA)
18
NS
Sensitive ( )
mA Input 3
7
+VE
+24 VDC
mV Input 3
19
S
Sensitive (+)
8
VE
0 VDC
20
01
Signal
9
Sig
Signal (4 20 mA)
21
NS
Sensitive ( )
mA Input 4
10
+VE
+24 VDC
mV Input 4
22
S
Sensitive (+)
11
VE
0 VDC
23
01
Signal
12
Sig
Signal (4 20 mA)
24
NS
Sensitive ( )
Table 9. Dual Input Module Connections
5.2.13 mA Output Module Connections
Label
Terminal
Identifier
Field Device
mA Out 1
1
I+
24 VDC, 4 20 mA, R
Loop
: 33 700
2
I-
GND
mA Out 2
3
I+
24 VDC, 4 20 mA, R
Loop
: 33 700
4
I-
GND
mA Out 3
5
I+
24 VDC, 4 20 mA, R
Loop
: 33 700
6
I-
GND
mA Out 4
7
I+
24 VDC, 4 20 mA, R
Loop
: 33 700
8
I-
GND
Table 10. mA Output Module Connections
mA Output Module Connections
Touchpoint Plus
mA Input
Module