MAN0984_Iss 4_01/19 Touchpoint Plus
Pt. No. 3011M5001 72 Technical Handbook
7) Touch [Next].
8) Choose Count Reduction options. This option allows you to ignore faulty or inhibited detectors for Vote Count
purposes (See also 10 below):
9) Touch [Next] and then choose Inputs (Alarms A1, A2 & A3, Fault, Inhibit & Warnings) to auto-populate all the
available channels. Scroll down to see further channels and selectively un-tick if required.
10) Touch and enter Vote Count numbers if required (see box above).
11) Touch [Finish].
nfirmation from at least 2 detectors before it triggers a response.
in Fault mode or
Inhibit mode or both, and will trigger an event when one or more detectors (not in fault or inhibit) are triggered.
Non-voting detectors are not affected by Vote Count Reduction.
Vote count reduction is applicable for only the relays configured to alarm event.