Chapter 10 Parameter Shenzhen Hpmont Technology Co., Ltd.
- 98 - HD09-S Series User Manual V1.1
Ref. Code
Function
Setting Range
Default
Unit
Attribute
Setting
F15.36 Set running time
0 - 65535h
0: Preset operating time is disabled
0h 1h
F15.37
Setted count value reach
preset
F15.38 - 9999 0 1
F15.38
Specified count value
reach preset
0 - F15.37 0 1
F15.43 The output terminal delay 0.0 - 100.0s 0.0s 0.1s
×
F16: Analogue Input / Output Terminal Parameter
F16.00
Keypad potentiometer
function
0: Resevered
2: Frequency setting
3: Auxiliary frequency setting
4: Process PID setting
5: PID feedback process
9: Motor FWD rotation torque limit
10: Motor reversing motor torque limit
11: Motor FWD regenerative torque
limit
12: Motor REV regenerative torque limit
0 1
×
F16.01 AI function 2 1
×
F16.05 AI offset -100.0 - 100.0% 0.0% 0.1%
F16.06 AI gain 0.00 - 10.00 1.00 0.01
F16.07 AI filter time 0.01 - 10.00s 0.05s 0.01s
F16.17 Max. input pulse frequency 0 - 50000Hz 10000Hz 1Hz
F16.18 Enter the pulse filter time 0.01 - 10.00s 0.05s 0.01s
F16.19 AO function
0: Reserved
2: Preset frequency (0 - max. output
frequency)
3: Motor rpm (0 - the max. output
frequency corresponds to the speed)
5: Output current (0 - 2 times the motor
rated current)
11: Output voltage (0 - 1.2 times the
inverter rated voltage)
12: DC bus voltage (0 - 2.2 times the
inverter rated voltage)
14: AI input (after processing)
2 1
F16.21 DO function 0 1
F16.22 AO offset -100.0 - 100.0% 0.0% 0.1%
F16.23 AO gain 0.0 - 200.0% 100.0% 0.1%