Shenzhen Hpmont Technology Co., Ltd. Chapter 10 Parameter
HD09-S Series User Manual V1.1 - 101 -
Ref. Code
Function
Setting Range
Default
Unit
Attribute
Setting
F19: Enhancement Parameters
F19.00
Auxiliary frequency setting
channel selection
0: No auxiliary channel
1: Operation keypad setting
2: Terminal setting
3: SCI communication settings
4: Analog setting
5: Terminal pulse setting
6: PID output setting
0 1
F19.01
Main and auxiliary setting
operation
0: Main setting + auxiliary setting
1: Main Settings - auxiliary settings
0 1
F19.02 Auxiliary setting coefficient 0.00 - 9.99 1.00 0.01
F19.03
Digital auxiliary frequency
initial value
0.00 - F00.06 0.00Hz 0.01Hz
F19.04
Digital auxiliary frequency
control selection
Unit: Power-down storage options
0: Auxiliary frequency is not stored
when power is lost
1: Power down stores the auxiliary
frequency
Ten: Stop frequency processing
0: Maintain auxiliary frequency after
stop
1: Auxiliary frequency returns to F19.03
after stop
00 1
F19.05
Set the frequency ratio
adjustment selection
0: Do not adjust
1: Relative max. output frequency
(F00.06) adjustment
2: Relative to the current frequency
adjustment
1 1
F19.06
Set the frequency scaling
factor
0.0 - 200.0% 100.0% 0.1%
F19.07
Cooling fan control
options
0: Auto stop mode
1: Immediate stop mode
2: The fan is runningwith power on
0 1
F19.08
Cooling fan control delay
time
0.0 - 600.0s 60.0s 0.1s
F19.10 Zero-frequency threshold 0.00Hz - F00.08 1.00Hz 0.01Hz