The gas generated by a burning battery may irritate your eyes, skin, and throat.
Take protective measures promptly.
Install batteries in a dry area. Do not install them under areas prone to water
leakage, such as air conditioner vents, ventilation vents, feeder windows of the
equipment room, or water pipes. Ensure that no liquid enters the equipment to
prevent faults or short circuits.
Before installing and commissioning batteries, prepare re extinguishing facilities,
such as re ghting sands and carbon dioxide re extinguishers, according to
construction standards and regulations. Before putting the battery room into
operation, ensure that it is equipped with a
re extinguishing system that
complies with local laws and regulations, has been constructed and commissioned,
and can work in automatic and manual control modes.
Before unpacking batteries, ensure that the packing cases are intact and correctly
placed according to the labels on the packing cases during their storage and
transportation. Do not place a battery upside down or vertically, lay it on one side,
or tilt it. Stack the batteries according to the stacking requirements on the packing
cases. Ensure that the batteries do not fall or get damaged. Otherwise, they will
need to be scrapped.
After unpacking batteries, place them in the required direction. Do not place a
battery upside down or vertically, lay it on one side, tilt it, or stack it. Ensure that
the batteries do not fall or get damaged. Otherwise, they will need to be scrapped.
Tighten the screws on copper bars or cables to the torque specied in this
document. Periodically
conrm whether the screws are tightened, check for rust,
corrosion, or other foreign objects, and clean them up if any. Loose screw
connections will result in excessive voltage drops and batteries may catch
re
when the current is high.
FusionDC1000A Prefabricated All-in-One Data
Center
Commissioning Guide (IT Scenario) 1 Safety Information
Issue 02 (2022-12-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 19