Step 3 Reset the ASD.
1. Rotate the knob switch Mode to position 0.
2. Press the Set/Res button to start the reset.
3. Wait until the two airow LEDs in the middle turn on.
4. Rotate the knob switch Mode to position 1.
5. Press the Set/Res button to
nish the reset.
Step 4 Release smoke in the protected area using the smoke pistol. Verify that the ASD
alarm indicator lights up, and that an alarm is generated in the management
system.
After the operation is complete, press the reset button to reset the ASD
----End
4.7 (Optional) NetEco Management
4.7.1 Preparations and WebUI Login
Prerequisites
● Supported operating system: Windows 7 and later versions
● It is recommended that the screen resolution be 1366 x 768 or higher.
● Browser: Chrome, Firefox 32, Internet Explorer 11 or later
Procedure
Step 1 Connect a network cable between the PC network port and the WAN1 port
(protected by a security mechanism) on the ECC800-Pro.
Table 4-5 Default IP addresses for the WAN and LAN ports on the ECC800-Pro
Port
Default IP Address
WAN1 192.168.8.10
WAN2 192.168.0.10
192.168.248.10 (FusionModule500/800)
LAN1 and LAN2 192.168.248.10
FusionDC1000A Prefabricated All-in-One Data
Center
Commissioning Guide (IT Scenario) 4 Commissioning Core Devices