Step 2 Press and hold the POWER ON/OFF button on the BCU for more than 5s. (Perform
this operation for multiple SmartLi cabinets one by one.)
NO TICE
If batteries will not be charged for more than one month after they are fully
charged and powered
o, remove the BCU to prevent battery module damage
due to overdischarge.
If battery modules are stored without being fully charged, charge them
according to the requirements in Transportation and Storage > Battery
Cabinet Storage with Low SOC to prevent battery module damage due to
overdischarge.
----End
4.2.3 Performing EPO
NO TICE
After EPO is triggered, there is no SmartLi output.
After EPO is triggered, the system reports a Battery cabinet shutdown alarm.
Press the external EPO switch that connects to the dry contact card or remove the
4-pin terminal on the EPO port of the dry contact card of the bypass unit.
4.2.4 Clearing the EPO State
Procedure
Step 1 Clear the EPO state. Ensure that the EPO button connected to the external EPO is
not in the EPO state.
Step 2 On the LCD screen, choose System Status > Alarms > Clear Faults. In the
displayed dialog box, tap Yes. The Battery cabinet shutdown alarm is cleared
successfully.
FusionDC1000A Prefabricated All-in-One Data
Center
Commissioning Guide (IT Scenario) 4 Commissioning Core Devices
Issue 02 (2022-12-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 42