When switching between dierent versions of the ECC800-Pro on your PC, you are
advised to clear the historical Internet Explorer cache. Failing to do so may cause some
information missed or exception after login. The following provides the details:
1. Open Internet Explorer and choose Tools > Internet Options > General.
2. Select Delete browsing history on exit and click Delete.
3. In the Delete Browsing History dialog box, select all options except Password,
and click Delete.
Step 5 Log in to the ECC800-Pro WebUI.
1. Enter https://
monitoring IP address
(such as https://192.168.8.10) in the
address box of the browser, and then press Enter to access the WebUI login
page.
Figure 4-10 WebUI login page
2. On the login page, enter the preset user name admin and preset password
Changeme, set the language, and click Log In.
– After the rst login, change the password in time to ensure account security and
prevent unauthorized network attacks, such as data tampering. The Company will
not be liable for any security issues caused by your failure to change the preset
password in time or password loss after changing.
– Change the password of the user account periodically.
– Record and keep the password properly. If you forgot the password, you will be
unable to log in to the WebUI.
– When the event
notication is congured and the password retrieval mode is
congured under user management, the password can be retrieved.
– An account is logged out due to timeout if no operation is performed within 10
minutes after system login.
– A maximum of three users can log in to the ECC800-Pro WebUI at the same time.
----End