● Before commissioning the re extinguishing system, remove the electrical
actuator from the container valve of the re extinguisher cylinder. This prevents
the extinguishant release due to misoperations, and prevents accidental
damage during the commissioning. After the commissioning of the
re
extinguishing system, reinstall the container valve to the electrical actuator.
● To avoid damage to the heat detector, keep a proper distance between the
heating device and the heat detector during the commissioning.
Preparations
Tools: multimeter, smoke pistol, heat gun, at-head screwdriver, Phillips
screwdriver, step ladder
Documents: re extinguishing drawings and parameters
Skill requirement: re engineer
Procedure
Step 1 Remove the electrical actuator from the re extinguisher cylinder.
If the electrical actuator is installed on the re extinguisher cylinder, remove the electrical
actuator from the container valve of the
re extinguisher cylinder.
Step 2 Switch on the input circuit breaker of the extinguishant control panel, and connect
the battery cables to the extinguishant control panel.
Step 3 Flip the key leftward to Auto & Manual, and set the extinguishant control panel
to Auto & Manual.
Figure 5-10 Auto & Manual indicator position
FusionDC1000A Prefabricated All-in-One Data
Center
Commissioning Guide (IT Scenario) 5 System Commissioning
Issue 02 (2022-12-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 73