No. Check That Check Result
3 The smart cooling product input voltage is within
the range of rated voltage ±10%, and the input
frequency is within the range of rated frequency
±3 Hz.
□ Passed □ Failed
4 The length of ground cables and power cables is
correct.
□ Passed □ Failed
5 Lugs for power cables and PGND cables are
soldered or crimped securely.
□ Passed □ Failed
6 Power cables and PGND cables are routed and
bundled separately from other cables.
□ Passed □ Failed
7 Lithium batteries are intact, free from damage,
cracks, and bulges.
□ Passed □ Failed
8 Lithium batteries are neat and clean, and do not
leak electrolyte.
□ Passed □ Failed
9 Lithium battery terminals are upright and free
from damage, break, and acid leakage.
□ Passed □ Failed
10 Lithium battery cables are connected correctly. □ Passed □ Failed
11 DIP switches on devices are correctly set. □ Passed □ Failed
Customer Sign:
Check Data:
FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S) 4 Installation Guide
Issue 02 (2021-06-30) Copyright © Huawei Technologies Co., Ltd. 101