To learn the mapping between the saturation pressure and the saturation
temperature of the R410A refrigerant, see Table 5-2.
Table 5-2 Mapping between the saturation pressure and the saturation
temperature for R410A
Saturation
Temperatu
re (°C)
Gauge
Pressure
(MPa)
Saturation
Temperatu
re (°C)
Gauge
Pressure
(MPa)
Saturation
Temperatu
re (°C)
Gauge
Pressure
(MPa)
0 0.7 19 1.31 38 2.21
1 0.73 20 1.35 39 2.27
2 0.75 21 1.39 40 2.33
3 0.78 22 1.4 41 2.39
4 0.81 23 1.47 42 2.45
5 0.84 24 1.51 43 2.51
6 0.87 25 1.56 44 2.57
7 0.9 26 1.60 45 2.63
8 0.93 27 1.65 46 2.7
9 0.96 28 1.69 47 2.76
10 0.99 29 1.74 48 2.83
11 1.02 30 1.79 49 2.9
12 1.05 31 1.84 50 2.97
13 1.09 32 1.89 51 3.04
14 1.12 33 1.94 52 3.11
15 1.16 34 1.99 53 3.19
16 1.19 35 2.04 54 3.26
17 1.23 36 2.1 55 3.34
18 1.27 37 2.15 - -
NO TE
1 MPa ≈ 10 bar ≈ 145 psi ≈ 10.2 kgf/cm
2
NO TICE
Users include admin (preset password: Changeme) and operator (preset
password: Changeme). To enter the diagnostic mode, log in as user admin.
FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S) 5 Power-On Commissioning
Issue 02 (2021-06-30) Copyright © Huawei Technologies Co., Ltd. 108

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule500 Smart and is the answer not in the manual?

Huawei FusionModule500 Smart Specifications

General IconGeneral
BrandHuawei
ModelFusionModule500 Smart
CategoryStorage
LanguageEnglish

Related product manuals