Maintenance
Area
Maintenance
Item
Operation Expected Result Troubleshootin
g
Monitor interface
(network
management
system or WebUI)
- Export smart
cooling product
logs, alarms,
temperature and
humidity data,
as well as the
operating status
and time of the
water sensor,
temperature
sensor, and
smoke sensor
from the
management
system. View the
historical alarms
generated in this
quarter and
select the most
common
ve
ones.
If an alarm is
generated,
handle the
alarm by
referring to
6.2.2
Management
System
Troubleshootin
g and 6.3
Alarm
References or
contacting
Huawei
technical
support.
Cable connection - The cable
connection is
secure.
Secure loose
cables.
- Cables are not
damaged.
Replace
damaged
cables.
Camera Camera
availability
On the ECC800-
Pro WebUI,
choose
Maintenance >
Manage Video >
Video Info to
enter the video
view page. Type
the camera name
or IP address to
nd the camera,
and click View to
view the real-
time monitoring
page.
The monitoring
page is properly
displayed after
you click View.
If the
monitoring
page is not
displayed after
you click View,
check that the
IP address is
correctly set,
and check cable
connections or
replace the
camera. For
details, see
6.4.3.5
Replacing a
Camera.
FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S) 6 O&M
Issue 02 (2021-06-30) Copyright © Huawei Technologies Co., Ltd. 152

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule500 Smart and is the answer not in the manual?

Huawei FusionModule500 Smart Specifications

General IconGeneral
BrandHuawei
ModelFusionModule500 Smart
CategoryStorage
LanguageEnglish

Related product manuals