Step 2 Remove the server node.
For details, see 8.3.3 Removing an XH321 V5.
Step 3 Place the server node on the ESD workstation.
Step 4 Remove the air duct.
For details, see 8.4.23 Removing the Air Duct.
Step 5 Take a spare memory module.
Step 6 Check the positions and installation guidelines of the memory modules.
For details, see 2.3.1.5 Memory Installation Positions.
Figure 8-43 Memory slots
Step 7 Install the memory module.
1. Open the two memory module ejectors on the memory slot.
Figure 8-44 Opening the memory module ejectors
2. Align the edge connector of the memory module with the alignment key of
the memory slot, and insert the memory module in the slot.
The two memory ejectors are closed automatically after the memory module
is
rmly seated.
NO TE
Do not touch the edge connector on a memory module with bare hands. Before
installing a memory module, ensure that the edge connector is not contaminated.
FusionServer Pro XH321 V5 Server Node
Maintenance and Service Guide 8 Parts Replacement
Issue 17 (2021-03-09) Copyright © Huawei Technologies Co., Ltd. 77