● The angle steel is stored in the carton in the control unit cabin. Open the door
of the control unit cabin to obtain it.
● There are four mounting holes where angle steel brackets contact the base.
Mark all mounting holes.
● Each angle steel bracket must be secured by two mounting holes. It is
recommended that the outer two mounting holes be used. If steel bars in a
concrete base block the drill bitor when the position deviation occurs during
the 
rst drilling, use the inner mounting holes.
● Ensure that the expansion bolts are tightened when securing the angle steel to
the base.
Figure 4-4 Securing the ESS
----End
Follow-up Procedure
After the ESS is hoisted and installed, verify the installation to ensure normal use
of products and smooth subsequent installation.
LUNA2000-2.0MWH-1H0, 2H0 Smart String ESS
User Manual 4 Installation