Parameter Description
Microgrid compatibility In the on-grid scenario, set this
parameter to Disable.
In the o-grid scenario, set this
parameter to Enable.
Grid Code Set the grid code of the country or
region where the devices are used.
NO TICE
For PCSs on the same DC bus, ensure that the settings of Running under Grid
connection state and Microgrid compatibility are the same.
Table 10-3 Parameter settings after device search (SmartLogger
V300R023C10 and later versions)
Parameter Description
Scenario under Arrays Operation
Scenario
In the on-grid scenario, set this
parameter to On-grid.
In the o-grid scenario, set this
parameter to O-grid.
In the on/o-grid switchover
scenario, set this parameter to
On/O-grid.
Grid Code Set the grid code of the country or
region where the devices are used.
Working mode under Parameter
Conguration
Set this parameter to PQ for the
current source mode.
Set this parameter to VSG for the
voltage source mode.
Microgrid compatibility under
Parameter Conguration
In the on-grid scenario, set this
parameter to Disable.
In the o-grid scenario, set this
parameter to Enable.
Active Power Baseline (kW) under
Parameter Conguration
Set the lower limit of the maximum
apparent power, which is also used
as the baseline for active power
scheduling.
Apparent Power Baseline (kVA)
under Parameter Conguration
Set the upper limit of the maximum
active power, which is also used as
the baseline for reactive power
scheduling.