Parameter Description
Maximum Overload Active Power
(kW) under Parameter
Conguration
Set the maximum overload active
power for grid forming.
Maximum Overload Apparent
Power (kVA) under Parameter
Conguration
Set the maximum overload apparent
power for grid forming.
NO TICE
For PCSs on the same DC bus, ensure that the settings of Scenario under
Arrays Operation Scenario and Microgrid compatibility are the same.
Step 4 Connect to a power meter, and set Meter usage to Export+import meter.
Figure 10-12 Setting meter parameters
Step 5 Connect to EMIs.
Figure 10-13 Setting EMI parameters
LUNA2000-(97KWH-1H1, 129KWH-2H1,
161KWH-2H1, 200KWH-2H1) Smart String ESS
User Manual 10 Commissioning the ESS (SmartLogger WebUI)
Issue 10 (2023-11-07) Copyright © Huawei Digital Power Technologies Co., Ltd. 144