Figure 6-97 Installing a disk module
Step 8 Wait approximately two minutes and view the status indicator on the disk module
to determine whether the disk module has been successfully installed. Figure 6-98
shows the location of the status indicator on the disk module.
If the indicator is steady green, the disk module has been successfully
installed.
If the indicator is steady red or
o, the newly installed disk module is faulty,
the slot for the disk module is faulty, or the disk module is incorrectly
installed.
Figure 6-98 Status indicator on a disk module
Step 9 After the disk module has been successfully installed, slide the enclosure into the
cabinet slowly and fasten the two screws on the panel, as shown in Figure 6-99.
OceanStor V5 Series
Parts Replacement 6 Replacing CRUs
Issue 15 (2019-12-30) Copyright © Huawei Technologies Co., Ltd. 99