● System undervoltage (%)
Species the lower alarm threshold in relative to the rated voltage. The value
ranges from 75 to 95.
● Undervoltage ack.time (s)
Species the duration for conrming an undervoltage alarm. The value ranges
from 1 to 10.
● Overload (%)
Species the overload alarm threshold in relative to the rated load. The value
ranges from 100 to 120.
● Overload ack.time (s)
Species the duration for conrming an overload alarm. The value ranges from 1
to 10.
● Overfrequency (Hz)
Species the overfrequency alarm threshold in relative to the rated frequency. The
value ranges from 1 to 10.
● Overfrequency ack.time (s)
Species the duration for conrming an overfrequency alarm. The value ranges
from 1 to 10.
● Upper load cur. thre. (%)
Species the upper alarm threshold in relative to the rated current. The value
ranges from 80 to 100.
● Lower Load cur. thre. (%)
Species the lower alarm threshold in relative to the rated current. The value
ranges from 30 to 80.
7.4.3.6 Setting Wizard
On the Settings screen, tap Setting Wizard to access the screen.
PDU8000 Modular Precision PDC V2.0
User Manual 7 MDU Commissioning Guide
Issue 04 (2021-04-13) Copyright © Huawei Technologies Co., Ltd. 94