Procedure
Step 1 Push the fuse handle up outwards.
Step 2 Remove the faulty fuse.
Figure 8-17 Removing a fuse
Step 3 Install a new fuse, and reinstall the handle.
----End
8.4.6 Replacing a monitoring board
Prerequisites
● Tool: Phillips screwdriver
● Materials: new monitoring board
Procedure
Step 1 Loosen the two bolts on the monitoring board, as shown by (1) in Figure 8-18.
Step 2 Open the two crowbars on the monitoring board, as shown by (2) in Figure 8-18.
Step 3 Gently pull out the monitoring board, as shown by (3) in Figure 8-18.
PDU8000 Modular Precision PDC V2.0
User Manual 8 Maintenance Guide
Issue 04 (2021-04-13) Copyright © Huawei Technologies Co., Ltd. 133