Feature Description
Cost-saving and exible to deliver and deploy thanks
to a compact design
Compatible with cabinets of low to high power density
(Optional) Hot-swap branch switches, making
maintenance and capacity expansion convenient
Safe and reliable Certied by CCC, CE, and TL
Proper connection between main metal components in
the power cabinet; resistance less than 0.1 ohm
Hot-swap monitoring board; strong- and weak-current
separation
Intelligent monitoring Strong networking capability for teleindication,
telemetry, telecontrol, and teleadjusting
Real-time monitoring and alarm reporting
(Optional) Temperature monitoring
Capacity expansion (Optional) Capacity expansion for hot-swap circuit
breakers with power-on
Fire linkage (Optional) The non-re extinguishing power supply is
cut o by using 24 V DC before extinguishant is
released.
 
3.5 Technical Specications
Table 3-2 Technical specications
Item
Specications
H x W x D (mm) 2000 x 600 x 1100, 2000 x 600 x 1200, 2200 x 600 x 1200,
2500 x 600 x 1200
Weight (kg) < 450
Rated operating
voltage (V)
208/380/400/415 (line voltage)
Rated insulation
voltage (V)
500
Rated frequency
(Hz)
50/60
Rated operating
current (A)
630/400/250/160
PDU8000 Modular Precision PDC V2.0
User Manual 3 Overview
Issue 04 (2021-04-13) Copyright © Huawei Technologies Co., Ltd. 14