5.4.2 Power Cable Specications
YJV 5-core cables are recommended. When the ambient temperature is 40°C, the
conductor working temperature cannot exceed 90°C.
For the installation torque for power connection of involved electrical parts, see
the
specications of the electrical parts. If the torque is not specied, see the
torque requirements listed in the following table.
Table 5-7 Power cable specications
Wiring
Terminal
Rated
Current (A)
Recommend
ed Cross-
Sectional
Area (mm
2
)
Terminal/Bolt
Specications
Recommended
Torque (N·m)
Power input
(L/N)
160 50 DT-M10 27
250 95 DT-M12 47
400 185 DT-M16 120
630 2 x 185 DT-M16 120
Power input
(PE)
160 25 DT-M10 27
250 50 DT-M10 27
400 95 DT-M12 47
630 2 x 95 DT-M12 47
AC output
(L)
< 10 2.5 Cord end
terminal
(crimping
screw
specication:
M4)
1.2
10 ≤ I ≤ 40 6 Cord end
terminal
(crimping
screw
specication:
M4)
1.2
40 < I ≤ 63 10 Cord end
terminal
(crimping
screw
specication:
M4)
1.2
AC output
(N/PE)
< 10 2.5 OT-M6 4.5
10 ≤ I ≤ 40 6 OT-M6 4.5
PDU8000 Modular Precision PDC V2.0
User Manual 5 Installation Guide
Issue 04 (2021-04-13) Copyright © Huawei Technologies Co., Ltd. 49