Table 3-14 SPD functional parameters
Item Description
Function Provides lightening and transient voltage surge
protection.
Specications Operating temperature: -40°C to +70°C
Operating humidity: 5%-95%RH
Nominal discharge current In (8/20 µs) = 20 kA
Maximum discharge current Imax (8/20 µs) = 40 kA
Voltage protection level Up (20 kA, 8/20 μs) ≤ 1.8 kV
(L-N)/≤ 1.0 kV (N-PE)
PDU8000 Modular Precision PDC V2.0
User Manual 3 Overview
Issue 04 (2021-04-13) Copyright © Huawei Technologies Co., Ltd. 30