EasyManua.ls Logo

Huawei RMS-SNMP01A - Page 42

Huawei RMS-SNMP01A
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RMS-SNMP01A SNMP Card
User Manual
4 Managing the UPS on the WebUI
Copyright © Huawei Technologies Co., Ltd.
34
Figure 4-14 uses the UPS2000-G as an example. The UPS2000-A does not provide battery management
functions. Only startup and shutdown operations can be performed on the UPS2000-A.
Figure 4-14 Control page
Table 4-4 Definition of battery tests
Test Name
Definition
Shallow discharge test
A manual shallow discharge test designed to
test the short-time backup capacity after
long-time (60 days by default) battery
charging.
Capacity test
A manual deep discharge test designed to
obtain the battery discharge performance
data.
You can perform the following operations on the Control page:
When the shallow discharge test conditions are met, click Start to perform a shallow
discharge test.
When the capacity test conditions are met, click Start to perform a capacity test.
After a capacity test or shallow discharge test starts, click Stop to stop the test.
When batteries are in the float charging state, click Manual equalized charging to start
equalized charging.
When batteries are in the equalized charging state, click Manual float charging to start
float charging.