Figure 7-8 IPS test
Table 7-5 IPS test type
IPS Test Type
Description
Maximum voltage
over 10 min
(59.S1)
The default maximum voltage over 10 min protection
threshold is 253 V (1.10 Vn), and the default protection
time threshold is 3s.
Maximum
overvoltage
(59.S2)
The default overvoltage protection threshold is 264.5 V
(1.15 Vn), and the default protection time threshold is 0.2s.
Minimum
undervoltage
(27.S1)
The default undervoltage protection threshold is 195.5 V
(0.85 Vn), and the default protection time threshold is 1.5s.
Minimum
undervoltage
(27.S2)
The default undervoltage protection threshold is 34.5 V
(0.15 Vn), and the default protection time threshold is 0.2s.
Maximum
overfrequency
(81.S1)
The default overfrequency protection threshold is 50.2 Hz,
and the default protection time threshold is 0.1s.