Check Item Check Method Maintenance
Interval
Cleanness of
air intake and
exhaust vents
Check periodically whether there is
dust or foreign objects at the air intake
and exhaust vents.
Power o the
inverter and remove
dust and foreign
objects. If necessary,
remove the bae
plates from the air
intake and exhaust
vents for cleaning.
Once every 6 to 12
months (or once
every 3 to 6 months
based on the actual
dust conditions in
the environment)
System
running status
● Check whether the inverter is
damaged or deformed.
● Check whether the inverter
generates abnormal sound during
operation.
● Check whether all inverter
parameters are correctly set during
operation.
Once every 6
months
Electrical
connection
● Check whether cables are
disconnected or loose.
● Check whether cables are damaged,
especially whether the cable sheath
that contacts a metal surface is
damaged.
6 months after the
rst commissioning
and once every 6 to
12 months after that
Grounding
reliability
Check whether the PE cable is securely
connected.
6 months after the
rst commissioning
and once every 6 to
12 months after that
Sealing Check whether all terminals and ports
are properly sealed.
Once a year
8.2 System Power-O
SUN2000-(5K-12K)-MAP0 Series
User Manual 8 System Maintenance
Issue 01 (2024-05-13) Copyright © Huawei Digital Power Technologies Co., Ltd. 112