Alar
m ID
Alarm
Name
Alarm
Severity
Possible
Causes
Troubleshooting
2065 Upgrad
e failed
or
version
mismat
ch
Minor Cause ID = 1–4,
7
The upgrade is
not completed
normally.
1. Perform an upgrade again.
2. If the upgrade fails several
times, contact your dealer or
Huawei technical support.
6144
0
Faulty
monitor
ing unit
Minor Cause ID = 1
● The ash
memory is
insucient.
● The ash
memory has
bad sectors.
Turn o the AC output switch
and DC input switch, and then
turn them on after 5 minutes. If
the alarm persists, replace the
monitoring board or contact
your dealer or Huawei technical
support.
2067 Faulty
power
collecto
r
Major Cause ID = 1
The power
meter is
disconnected.
1. Check whether the congured
power meter model is the
same as the actual model.
2. Check whether the
communications parameters
of the power meter are the
same as the RS485
congurations of the inverter.
3. Check whether the power
meter is powered on and
whether the RS485
communications cable is
connected.
SUN2000-(12K-25K)-MB0 Series
User Manual 7 System Maintenance
Issue 01 (2023-04-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 95