Item Description Default Value Value Range
Frequency
level
Set the system output
frequency level. If this
parameter is set to
Automatic, the system
output frequency is 50
Hz when the power-on
bypass frequency ranges
from 40 Hz to 55 Hz,
and the system output
frequency is 60 Hz when
the power-on bypass
frequency ranges from
55 Hz to 70 Hz
(excluding 55 Hz). This
parameter is
congurable only after
the inverter is shut
down.
50 Hz 50 Hz, 60 Hz,
Automatic
Volt. adj.
coef.
You can adjust the
inverter rated output
voltage. Press <cf
id="Bold">+</cf> or <cf
id="Bold">–</cf> to
increase or decrease the
output voltage.
0% ±5%, ±4%, ±3%,
±2%, ±1%,0%
Converter
mode
Species whether to
enable converter mode.
In converter mode, the
output voltage and
frequency are xed to
the preset values. This
parameter is
congurable only after
the inverter is shut
down.
NOTICE
In converter mode, the
bypass output and the
maintenance bypass are
unavailable. If you shut
down the inverter, the UPS
stops supplying power to
loads.
Disabled Disabled, Enabled
● Bypass screen
UPS2000-G-(6 kVA-20 kVA)
User Manual 4 Control Panel