Item Description Default
Value
Value Range
Frequency
range
Bypass frequency range.
When the dierence
between the bypass
input frequency and the
rated frequency is
greater than this value,
the system determines
that the bypass
frequency is abnormal
and that the bypass is
unavailable.
The Frequency range
parameter is associated
with the ECO frequency
range and must be
greater than the current
ECO frequency range.
This parameter is
congurable only after
the inverter is shut
down.
±2 Hz
±0.5 Hz, ±1 Hz, ±2 Hz,
±3 Hz, ±4 Hz, ±5 Hz,
±6 Hz
ECO screen
Figure 4-31 ECO screen
NO TE
You can use the ECO function only if power grid conditions are good and the voltage
and frequency uctuation is within the specied ECO voltage and frequency range.
UPS2000-G-(6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 73

Table of Contents

Other manuals for Huawei UPS2000-G Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G Series and is the answer not in the manual?

Huawei UPS2000-G Series Specifications

General IconGeneral
Frequency50/60 Hz
Output Power Factor0.9
Humidity0% to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model
Capacity1 kVA, 2 kVA, 3 kVA
Input Voltage220 Vac (120 Vac/208 Vac/230 Vac/240 Vac)
Output Voltage220/230/240 VAC
EfficiencyUp to 95%
TopologyDouble conversion online
Battery TypeSealed Lead Acid
Communication PortsUSB, RS232
Optional CommunicationSNMP
Operating Temperature0°C to 40°C

Related product manuals