Table 4-21 ECO settings
Item Description Default
Value
Value Range
Max.
voltage
Upper threshold for the ECO
voltage. In ECO mode, when the
dierence between the bypass
voltage and the rated voltage is
greater than this value, the
system determines that the ECO
voltage is abnormal and transfers
to normal mode. This parameter
is
congurable only after the
inverter is shut down.
10% 5%, 6%, 7%,
8%, 9%, 10%
Min.
voltage
Lower threshold for the ECO
voltage. In ECO mode, when the
dierence between the bypass
voltage and the rated voltage is
lower than this value, the system
determines that the ECO voltage
is abnormal and transfers to
normal mode. This parameter is
congurable only after the
inverter is shut down.
10% 5%, 6%, 7%,
8%, 9%, 10%
Frequen
cy
range
ECO frequency range. In ECO
mode, when the dierence
between the bypass frequency
and the rated frequency is beyond
this range, the system determines
that the ECO frequency is
abnormal and transfers to normal
mode.
The Frequency range parameter
is associated with the bypass
frequency range and must be less
than the current bypass frequency
range. This parameter is
congurable only after the
inverter is shut down.
±2 Hz ±0.5 Hz, ±1
Hz, ±2 Hz,±3
Hz
Single
UPS
ECO
Determine whether to support
ECO mode on a single UPS (ECO
mode is not supported in a
parallel system).
Disabled Disabled,
Enabled
● Power Segment screen
UPS2000-G-(6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 21 (2022-10-13) Copyright © Huawei Technologies Co., Ltd. 74