P25
To edit the Emergency Scene
1. From the Conguration menu, highlight the ‘Emer-
gency Scene Edit’ option and press the
ENT
button.
The display will show a list of the congured Output
settings:
2. You can alter Output levels collectively or individually,
as required:
Collectively - Highlight the ‘All Outputs’ option and
either type the required level using the keypad or use
the
or
buttons to adjust the current value for
all Outputs and press the
ENT
button.
Individually - Highlight the required Output and either
type the required level using the keypad or use the
or
buttons to adjust the current value and
press the
ENT
button to set the Output value.
3. To exit, press the
ESC
button to save all changes and
return to the previous screen.
Emergency Scene
All Outputs
Output190%
Output290%
Output390%
What is the Emergency Scene?
The Emergency Scene is a group of settings for one
or more Outputs that will only be used in cases of
emergency, generally to provide evacuation lighting.
The Emergency Scene can be invoked in any of four
ways:
When a Contact Closure Input places the SCRP
Switched Relay Controller into the Emergency
State (a condition where most CAN messages
are ignored and the Emergency Scene is dis-
played until such time that the Emergency State
is cancelled).
During the restoration of the supply following a
power outage (dependant on the setting within
the Congure Outputs Startup Action option -
see page 22).
By using the ‘Operation’ > ‘Output Override’ >
‘Select Scene’ option and selecting Scene 132.
On receipt of an iCANnet Emergency message.
Objective: To congure the desired Output levels for the Emergency Scene.
The Emergency Scene is pre-congured to set all Output levels to 100% or on. If you do not need to edit the
Emergency Scene as part of your commissioning process, then go straight to Step 10.
Step 9: Edit the Emergency Scene

Questions and Answers: