AUDAX TOP ErP
15
Menu Service -> Integration
Menu item Description Range Default
Electrical integration
It establishes the type of integration in the system: “Sys.” enables the system integra-
tion, “San” the DHW integration, “San+Sys.” enables both integrations
- None
- Sys.
- N.A.
- N.A.
- N.A.
- San
- San + Sys.
None
Contemp. Temp.
intgr.
Temperature threshold below which integration is activated and the heat pump
maintained on.
-20 ÷ +15 °C -20 °C
Min. temp. of inte-
gration
Temperature threshold below which integration is activated and the heat pump is
switched o.
-20 ÷ +15 °C -20 °C
Waiting time integra-
tion
Standby to reach the set value before activating integration when outdoor tempera-
ture is below the previously set temperature values (minimum integration tempera-
ture and simultaneous integration temperature).
5 ÷ 120’ 60’
Counter reset H.P. Reset the number of operating hours of the heat pump Yes / No No
Integration device It establishes the type of integration in the system
- None
- Electrical re-
sistance
None
Min. Temp. of inte-
gration
Temperature threshold below which integration is activated and the heat pump is
switched o
-20 ÷ +30 °C -20 °C
Contemp. Temp.
integration
A value that is equal to, or higher than, the minimum integration temperature must
be set.
Activate central heating integration when the outdoor temperature is below the set
value, the set intake requested has not been reached, and the heat pump remains
active
0 ÷ 60 °C 20°C
Waiting time integra-
tion
Standby to reach the set value before activating integration when outdoor tempera-
ture is below the previously set temperature values (minimum integration tempera-
ture and simultaneous integration temperature)
0 ÷ 600’ 60’
Counter Reset H.P. Reset the number of operating hours of the heat pump Yes / No No
Menu Service -> Heat pump
Menu item Description Range
Flow temperature Instant outlet temperature from the system
Flow temp. system calc. Flow temperature requested by the generators
Comp. discharge temp. Current heat pump compressor temperature 0 ÷ 100 °C
Comp. suction temp. Compressor inlet temperature -20 ÷ 100 °C
BPHE refrigerant temp. Coolant temperature inside the plate heat exchanger -20 ÷ 100 °C
Coil refrigerant temp. Battery temperature -20 ÷ 100 °C
Outdoor Air Temp. Room temperature -20 ÷ 100 °C
Max freq. compressor Maximum frequency in current operating conditions 0 ÷ 200 Hz
Requested frequency Frequency requested by the control board 0 ÷ 200 Hz
Actual frequency Current compressor frequency 0 ÷ 200 Hz
Compressor runtime Number of hours of operation of the compressor
N.B. PARAMETERS ONLY VALID FOR AUDAX TOP 18 - 21 ErP
N.B. PARAMETERS ONLY VALID FOR AUDAX TOP 6 - 8 - 12 - 16 ErP
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua
voltar.com.ua

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Immergas AUDAX TOP ErP Series and is the answer not in the manual?

Immergas AUDAX TOP ErP Series Specifications

General IconGeneral
BrandImmergas
ModelAUDAX TOP ErP Series
CategoryHeat Pump
LanguageEnglish

Related product manuals