INSTALLER
USERMAINTENANCE TECHNICIAN
TECHNICAL DATA
Parameter
ID
Description Range Default
Customised
value
R 06
Outdoor temperature for Zone 2
low temperature zone max. CH
ow
Establishes the outdoor temperature at which to
have the maximum ow temperature of zone 2
-15 ÷ 25 °C -5
R 07
Outdoor temperature for Zone 2
low temperature zone min. CH
ow
Establishes the outdoor temperature at which to
have the minimum ow temperature of zone 2
-15 ÷ 25 °C 25
R 08
Zone 2 low temperature zone
maximum central heating
Denes the maximum ow temperature in zone 2
room central heating mode
20 ÷ 65 40
R 09
Zone 2 low temperature zone
minimum central heating
Denes the minimum ow temperature in zone 2
room central heating mode
20 ÷ 65 25
R 10
Zone 1 outdoor temperature for
minimum cooling ow
Establishes the maximum outdoor temperature at
which to have the minimum ow temperature in
zone 1 cooling mode
20 ÷ 40 35
R 11
Outdoor temperature for Zone 1
maximum cooling ow
Establishes the minimum outdoor temperature at
which to have the maximum ow temperature in
zone 1 cooling mode
20 ÷ 40 25
R 12 Zone 1 minimum cooling
Denes the minimum ow temperature in zone 1
room cooling mode
05 ÷ 20 7
R 13 Zone 1 maximum cooling
Denes the maximum ow temperature in zone 1
room cooling mode
05 ÷ 25 12
R 14
Outdoor temperature for Zone 2
low temperature zone min
cooling ow
Establishes the outdoor temperature at which to
have the minimum ow temperature of zone 2
20 ÷ 40 35
R 15
Outdoor temperature for Zone 2
low temperature zone max
cooling ow
Establishes the outdoor temperature at which to
have the maximum ow temperature of zone 2
20 ÷ 40 25
R 16
Zone 2 low temperature zone
minimum cooling
Denes the minimum ow temperature in zone 2
room cooling mode
05 ÷ 20 18
R 17
Zone 2 low temperature zone
maximum cooling
Denes the maximum ow temperature in zone 2
room cooling mode
05 ÷ 25 20
R 21
Outdoor temperature for max
CH ow zone 3
Establishes the outdoor temperature at which to
have the maximum ow temperature of zone 3
-15 ÷ 25 -5
R 22
Outdoor temperature for min
CH ow zone 3
Establishes the outdoor temperature at which to
have the minimum ow temperature of zone 3
-15 ÷ 25 25
R 23
Zone 3 maximum central
heating
Denes the maximum ow temperature in zone 3
room central heating mode
20 ÷ 65 40
R 24
Zone 3 minimum central
heating
Denes the minimum ow temperature in zone 3
room central heating mode
20 ÷ 65 25
R 25
Outdoor temperature for Zone 3
low temperature zone min
cooling ow
Establishes the outdoor temperature at which to
have the minimum ow temperature of zone 3
20 ÷ 40 35
R 26
Outdoor temperature for Zone 3
low temperature zone max
cooling ow
Establishes the outdoor temperature at which to
have the maximum ow temperature of zone 3
20 ÷ 40 25
R 27
Zone 3 low temperature zone
minimum cooling
Denes the minimum ow temperature in zone 3
room cooling mode
05 ÷ 20 18
R 28
Zone 3 low temperature zone
maximum cooling
Denes the maximum ow temperature in zone 3
room cooling mode
05 ÷ 25 20

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Immergas MAGIS COMBO PLUS V2 Series and is the answer not in the manual?

Immergas MAGIS COMBO PLUS V2 Series Specifications

General IconGeneral
BrandImmergas
ModelMAGIS COMBO PLUS V2 Series
CategoryHeat Pump
LanguageEnglish

Related product manuals