4.4 ASSEMBLY OF ADDITIONAL BOILER MANIFOLD KIT FOR VICTRIX PRO V2 100120 EU
e extension kits make it possible to complete cascade installation, and you must have one for each boiler being connected, according to gure 21 (max of 5 boilers
in cascade).
Replace the intake closing cap on the boiler with the intake stub kit (1).
To make the connections (9) as shown in the gure according to the position of the boiler.
en engage them on the boiler until they are to the end stop, taking care to correctly orientate the clapet valve (10)
Connect the additional boiler manifolds (11) to the relative connections (9) and tighten the ring nut of each connection.
Connect the manifold with condensate drain (7) to the manifold (11).
Now connect the condensate drain trap (8) to the manifold (7).
Manifold kit composition Ø 200 Victrix Pro V2 100-120 EU additional boiler
Ref. Qty Description
9 1 Boiler connection DN110-125
10 1 Clapet DN125
11 1 Manifold DN200
boiler 1
boiler 2
boiler 3
boiler 4
boiler 5