EasyManuals Logo

Inovance MD520 Series Commissioning Guide

Inovance MD520 Series
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #72 background imageLoading...
Page #72 background image
Commissioning and Trial Run
‑71‑
Param
eter
Code
Parameter
Name
Value Default Description
A6‑40 Low level
judgment
threshold
when AI uses
as DI
1.0 V to 4.5 V 3.0 V This parameter defines the threshold for judging low
level when the AI is used as the DI.
A6‑41 AI1 gain ‑10.00 to +10.00 1.00 This parameter defines the AI1 analog sampling gain.
A6‑42 AI1 offset ‑10.00 V to +10.00 V 0.00 V This parameter defines the AI1 analog sampling offset.
A6‑43 AI1 denoising
threshold
0.0% to 100.0% 0.0% This parameter defines the AI1 denoising threshold. If
the absolute value of the difference between the
current input and the last input falls in the threshold
range, denoising will be applied.
A6‑44 AI1 dead zone
width
0.0% to 100.0% 0.0% This parameter defines the AI1 dead zone width. The
output is 0.0% within the dead zone range, which is
used to eliminate the fluctuation near zero.
A6‑47 AI2 gain ‑10.00 to +10.00 1.00 This parameter defines the AI2 analog sampling gain.
A6‑48 AI2 offset ‑10.00 V to +10.00 V 0.00 V This parameter defines the AI2 analog sampling offset.
A6‑49 AI2 denoising
threshold
0.0% to 100.0% 0.0% This parameter defines the AI2 denoising threshold. If
the absolute value of the difference between the
current input and the last input falls in the threshold
range, denoising will be applied.
A6‑50 AI2 dead zone
width
0.0% to 100.0% 0.0% This parameter defines the AI2 dead zone width. The
output is 0.0% within the dead zone range, which is
used to eliminate the fluctuation near zero.
A6‑53 AI3 gain ‑10.00 to +10.00 1.00 This parameter defines the AI3 analog sampling gain.
A6‑54 AI3 offset ‑10.00 V to +10.00 V 0.00 V This parameter defines the AI3 analog sampling offset.
A6‑55 AI3 denoising
threshold
0.0% to 100.0% 0.0% This parameter defines the AI3 denoising threshold. If
the absolute value of the difference between the
current input and the last input falls in the threshold
range, denoising will be applied.
A6‑56 AI3 dead zone
width
0.0% to 100.0% 0.0% This parameter defines the AI3 dead zone width. The
output is 0.0% within the dead zone range, which is
used to eliminate the fluctuation near zero.

Table of Contents

Other manuals for Inovance MD520 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Inovance MD520 Series and is the answer not in the manual?

Inovance MD520 Series Specifications

General IconGeneral
BrandInovance
ModelMD520 Series
CategoryDC Drives
LanguageEnglish

Related product manuals