Table 6-2  Selection of some electrical peripheral components for the MD880 series AC drive
Model
MD880-01S
Series
Recommended
Input IEC Cable
Speci󶍾cations
(mm
2
)
[1]
Recommended
IEC Ground
Cable (mm
2
)
Recommended
Output IEC
Cable (mm
2
)
Terminal
Width
of the
AC Drive
(mm)
Screw
Recommended
Fuse
Bussmann
Compliant with UL
Certi󶍾cation
Recommended
Contactor
Recommended
Circuit Breaker
Rated
Current
(A)
Model
Rated Current
(A)
Rated Current
(A)
Three-phase 380 V to 480 V, 50/60 Hz
MD880-
01S-0012-
4-B
3 x 2.5 2.5 3 x 2.5 4 M4 35 FWH-35B 25 32
MD880-
01S-0017-
4-B
3 x 4 4 3 x 4 6 M5 35 FWH-35B 25 32
MD880-
01S-0024-
4-B
3 x 4 4 3 x 4 6 M5 35 FWH-35B 25 32
MD880-
01S-0033-
4-B
3 x 6 6 3 x 6 10 M5 40 FWH-40B 32 40
MD880-
01S-0038-
4-B
3 x 10 10 3 x 10 15.0 M6 40 FWH-40B 32 40
MD880-
01S-0048-
4-B
3 x 10 10 3 x 10 15.0 M6 80 FWH-80B 65 80
MD880-
01S-0060-
4-B
3 x 16 16 3 x 16 15.0 M6 100
FWH-
100B
65 80
MD880-
01S-0078-
4-B
3 x 16 16 3 x 16 18.0 M6 100
FWH-
100B
65 80
MD880-
01S-0094-
4-B
3 x 16 16 3 x 16 18.0 M6 125
FWH-
125B
80 100
MD880-
01S-0116-
4-B
3 x 25 16 3 x 25 26.8 M8 150
FWH-
150B
95 160
MD880-
01S-0149-
4-B
3 x 50 25 3 x 50 26.8 M8 200
FWH-
200B
115 160
MD880-
01S-0183-
4-B
3 x 70 35 3 x 70 30.6 M12 250 FWH-250A 150 250
MD880-
01S-0217-4
3 x 95 50 3 x 95 30.6 M12 275 FWH-275A 170 250