1 Product Information
- 18 -
Item Specication
Environment
Requirements
Installation
location
Free from direct sunlight, dust, corrosive gas, combustible
gas, oil smoke, vapor, drip, or salt indoor
Altitude
Below 1000 m, derated by 1% per 100 m increase when the
altitude is above 1000 m
Maximum altitude: 3000 m
Operating ambient
temperature
Ambient temperature: -10℃ to +40℃ , derated by 1.5% per
1° C increase when the ambient temperature exceeds 40℃
Maximum temperature: 50° C
Storage
temperature
-20℃ to +60℃
Humidity Less than 95% RH, non-condensing
Vibration Lower than 5.9m/s
2
(0.6g)
Pollution degree PD2
Power system
TT/TN
IT (VDR and EMC screws removed)
Overvoltage
category
OVC III
IP rating
Structures T2 to T9: IP20
Structures T10 to T12: IP00
1.6 Derating
1) Ambient temperature and derating
When the temperature falls within 40℃ to 50℃ , the rated output current must be
derated by 1.5% for every 1° C increase. The output current can be calculated by
multiplying the current value given in the rating table by the derating factor (k):
L
ǫ ǫ
5
Figure 1-3 Ambient temperature and derating
2) Altitude and derating
When the altitude is 1000 m to 3000 m above the sea level, for every 100 m increase in
altitude, the output current of the AC drive must be derated by 1%.