3 Electrical Installation
- 57 -
6OTIJFMEFEQBSUNVTU
CFBTTIPSUBTQPTTJCMF
$SJNQFEPOUPUIFIPVTJOH
PSEFEJDBUFEHSPVEJOH
QPJOU
$POUSPM
NPEVMF
4IJFME
FOE
Figure 3-9 Requirements on shielded power cables
3.4.4 Connection of Shielded Power Cables
The input/output shielded power cable and shield inside the power unit must be in
large-area contact with the shield plate in the cabinet to achieve good EMC e󶍽ect. The
following 󶍾gure shows the connection diagram.
"$DPOEVDUPT
345
&.$TIJFMEJOHSJOH
PSTUSBQ
4IJFME
4IFBUI
$POEVDUTIJFMEJOH
TVQQPSU
1&CVT 1&
Figure 3-10 Connection of shielded power cables
3.5 Wring of the AC Drive
Preparation:
Power o󶍽 the device that will be installed in the cabinet.
Take all the necessary safety measures at the installation location.
Observe the "󶍾ve safety rules".
3.5.1 Standard Wiring Diagram
AC drives in structures T2 to T9 are connected to the HCU-51 control module
through high-speed RS422 communication cables. AC drives in structures T10 to