2 Mechanical Installation
- 28 -
Item Quantity
Enclosure
This product is installed in a cabinet and must be installed in the nal
system. The nal system must provide a reproof enclosure, electrical
enclosure, and mechanical enclosure, and comply with local laws and
regulations and relevant IEC standards.
%VTUBOEPJMEJSU
%JSFDUTVOMJHIU
4USPOHWJCSBUJPO
HSFBUFSUIBOH
)JHI
UFNQFSBUVSF
BOEIVNJEJUZ
5IFBNCJFOUUFNQFSBUVSFNVTU
CFǫUPǫ
$PNCVTUJCMFFYQMPTJWF
BOEDPSSPTJWFHBT
'MBNNBCMF
NBUFSJBM
%POPUJOTUBMMUIF"$ESJWFPOB
2.3 Installation Clearances and Direction
2.3.1 Installation Clearances
The clearance that needs to be reserved varies with the power rating of the MD880, as
shown in the following gure.
1) Installing a single AC drive
4JEFWJFX'SPOUWJFX
7FSUJDBMMZ
VQXBSE
6QXBSE
6QXBSE
Figure 2-3 Installation clearances of a single AC drive (structures T2 to T9)
Power Rating Dimension Requirements (mm)
5.5–30 kW A1 ≥ 10 B1 ≥ 200 C1 ≥ 20
37–45 kW A1 ≥ 50 B1 ≥ 200 C1 ≥ 20
55–200 kW A1 ≥ 50 B1 ≥ 300 C1 ≥ 20