2 Mechanical Installation
- 28 -
Item Quantity
Enclosure
This product is installed in a cabinet and must be installed in the 󶍾nal
system. The 󶍾nal system must provide a 󶍾reproof enclosure, electrical
enclosure, and mechanical enclosure, and comply with local laws and
regulations and relevant IEC standards.
%VTUBOEPJMEJSU
%JSFDUTVOMJHIU
4USPOHWJCSBUJPO
HSFBUFSUIBOH
)JHI
UFNQFSBUVSF
BOEIVNJEJUZ
5IFBNCJFOUUFNQFSBUVSFNVTU
CFǫUPǫ
$PNCVTUJCMFFYQMPTJWF
BOEDPSSPTJWFHBT
'MBNNBCMF
NBUFSJBM
%POPUJOTUBMMUIF"$ESJWFPOB
珞BNNBCMFPCKFDU
2.3 Installation Clearances and Direction
2.3.1 Installation Clearances
The clearance that needs to be reserved varies with the power rating of the MD880, as
shown in the following 󶍾gure.
1) Installing a single AC drive
4JEFWJFX'SPOUWJFX
7FSUJDBMMZ
VQXBSE
6QXBSE
6QXBSE
Figure 2-3 Installation clearances of a single AC drive (structures T2 to T9)
Power Rating Dimension Requirements (mm)
5.5–30 kW A1 ≥ 10 B1 ≥ 200 C1 ≥ 20
37–45 kW A1 ≥ 50 B1 ≥ 200 C1 ≥ 20
55–200 kW A1 ≥ 50 B1 ≥ 300 C1 ≥ 20