6 Options
- 127 -
6.6 Selection of the EMC Filter
6.6.1 Standard EMC lter
The standard EMC lter meets the EN 61800-3 C2 emission requirement of CE
certication. Connect the lter to ground reliably and ensure that the length of the
cable connecting the power supply unit and lter is less than 30 cm. For details about
the cables, see
"6.2 Selection of Cables, Circuit Breakers, and Contactors"
.
◆
The cable between the lter and the AC drive must be as short as possible
(within 30 cm). The lter and AC drive must be connected to the same
ground reference plane, and the lter must be reliably connected to
ground. Otherwise, desired ltering eect will not be achieved.
◆
For MD880-01S-0314-4 to MD880-01S-0751-4(-L), external lters are not
required. Their standard built-in EMC lters meet EN 61800-3 C3 emission
requirement of CE certication.
1) Appearance
Schaner FN3258 series lter
Schaner FN3359 series lter