2 Mechanical Installation
- 30 -
Power Rating Clearance Requirements (mm)
5.5–30 kW A ≥ 10
37–45 kW A ≥ 50
55–160 kW A ≥ 50
NOTE
For Structures T10 to T12, only one AC drive can be installed in a cabinet.
If multiple AC drives need to be installed side by side, contact Inovance or
the agent.
3) Installing AC drives above one another
In scenarios where AC drives are installed above one another, an air guide plate must be
installed to avoid overtemperature of the upper AC drive caused by heat generated by
the lower AC drive.
"JSHVJEFQMBUF
"$ESJWF
"$ESJWF
Figure 2-6 Installing AC drives (structures T2 to T9) above one another
NOTE
Structures T10 to T12 cannot be installed above one another.